Sampling Requirements

 

EAJSA Sampling Requirements

Revised 3/17/11

Parameters Bottle Type Sample Type Preservative Holding Time Sampling Method

NH3N*

Pint Plastic

Composite

H2SO4 to pH <2 cool to 4° C

28 days

EPA 350.1

Arsenic

Pint Plastic

Composite

HNO3 to pH <2 cool to 4° C

6 months

EPA 600 Method 200.7

BOD*

½ Gal. Plastic

Composite

None cool to 4° C

48 hours

STD Methods 20th Ed. 5210B

Cadmium

Pint Plastic

Composite

HNO3 to pH <2 cool to 4° C

6 months

EPA 600 Method 200.7

Chromium

Pint Plastic

Composite

HNO3 to pH <2 cool to 4°  C

6 months

EPA 600 Method 200.7

Color (Purity & Luminance)

Pint Plastic

Grab

None cool to 4° C

48 hours

SM #19 2120

Copper

Pint Plastic

Composite

HNO3 to pH <2 cool to 4 ° C

6 months

EPA 600 Method 200.7

Cyanide

Pint Plastic

Grab

NaOH to pH >12 cool to 4° C

14 days

STD Methods 20th Ed. 4500

Lead

Pint Plastic

Composite

HNO3 to pH <2 cool to 4 ° C

6 months

EPA 600 Method 200.7

Mercury

Pint Plastic

Composite

HNO3 to pH <2 cool to 4 ° C

6 months

EPA 600 Method 245.1

Nickel

Pint Plastic

Composite

HNO3 to pH <2 cool to 4° C

6 months

EPA 600 Method 200.7

Total Oil & Grease

Quart Glass

Grab

H2SO4 to pH <2 cool to 4° C

28 days

EPA 600 Method 1664 HEM

Total Petroleum Oil & Grease

Quart Glass

Grab

HCl to pH <2 cool to 4° C

28 days

EPA 600 Method 1664 SGT

Phenols

500 ml Amber Glass

Grab

H2SO4 to pH <2 cool to 4° C

28 days

EPA 600 Method 420.2

Silver

Pint Plastic

Composite

HNO3 to pH <2 cool to 4° C

6 months

EPA 600 Method 200.7

TSS*

Pint Plastic

Composite

None cool to 4° C

7 days

SM 20th 2540D

Zinc

Pint Plastic

Composite

HNO3 to pH <2 cool to 4° C

6 months

EPA 600 Method 200.7

Volatiles

3 - 40ml VOA Vials

Grab

Zero headspace HCl to pH <2 cool to 4° C

14 days

EPA Method 624

*Surchargeable Parameters


NOTES:
All sampling procedures must be in accordance with 40 CFR Part 136 and EAJSA Rules and Regulations.

Sample preservation must be performed immediately upon sample collection. Any self-monitoring conducted at the designated sample location (outlined in permit) which is in accordance with EPA approved procedure must be reported to the EAJSA (please note 1/28/00 memo). When using a different method for analysis you must notify the EAJSA prior.

References:
40 CFR Part 136

EPA's Industrial User Inspection And Sampling Manual for POTWs (EPA 831-B-94-001).

Easton Area Joint Sewer Authority Rules and Regulations.