EAJSA Sampling Requirements
Revised
3/17/11 |
| Parameters |
Bottle Type |
Sample Type |
Preservative |
Holding Time |
Sampling Method |
|
NH3N* |
Pint Plastic |
Composite |
H2SO4 to pH <2 cool to 4° C |
28 days |
EPA 350.1 |
|
Arsenic |
Pint
Plastic |
Composite |
HNO3 to pH <2 cool to 4° C |
6 months |
EPA 600 Method 200.7 |
|
BOD* |
½
Gal. Plastic |
Composite |
None cool to 4° C |
48 hours |
STD Methods 20th Ed. 5210B |
|
Cadmium |
Pint
Plastic |
Composite |
HNO3 to pH <2 cool to 4° C |
6 months |
EPA 600 Method 200.7 |
|
Chromium |
Pint
Plastic |
Composite |
HNO3 to pH <2 cool to 4° C |
6 months |
EPA 600 Method 200.7 |
|
Color
(Purity & Luminance) |
Pint
Plastic |
Grab |
None cool to 4° C |
48 hours |
SM #19 2120 |
|
Copper |
Pint
Plastic |
Composite |
HNO3 to pH <2 cool to 4 ° C |
6 months |
EPA 600 Method 200.7 |
|
Cyanide |
Pint
Plastic |
Grab |
NaOH to pH >12 cool to 4° C |
14 days |
STD Methods 20th Ed. 4500 |
|
Lead |
Pint
Plastic |
Composite |
HNO3 to pH <2 cool to 4 ° C |
6 months |
EPA 600 Method 200.7 |
|
Mercury |
Pint
Plastic |
Composite |
HNO3 to pH <2 cool to 4 ° C |
6 months |
EPA 600 Method 245.1 |
|
Nickel |
Pint
Plastic |
Composite |
HNO3 to pH <2 cool to 4° C |
6 months |
EPA 600 Method 200.7 |
|
Total
Oil & Grease |
Quart
Glass |
Grab |
H2SO4 to pH <2 cool to 4° C |
28 days |
EPA 600 Method 1664 HEM |
|
Total
Petroleum Oil & Grease |
Quart
Glass |
Grab |
HCl to pH <2 cool to 4° C |
28 days |
EPA 600 Method 1664 SGT |
|
Phenols |
500
ml Amber Glass |
Grab |
H2SO4 to pH <2 cool to 4° C |
28 days |
EPA 600 Method 420.2 |
|
Silver |
Pint
Plastic |
Composite |
HNO3 to pH <2 cool to 4° C |
6 months |
EPA 600 Method 200.7 |
|
TSS* |
Pint
Plastic |
Composite |
None cool to 4° C |
7 days |
SM 20th 2540D |
|
Zinc |
Pint
Plastic |
Composite |
HNO3 to pH <2 cool to 4° C |
6 months |
EPA 600 Method 200.7 |
|
Volatiles |
3 -
40ml VOA Vials |
Grab |
Zero headspace HCl to pH <2 cool to 4° C |
14 days |
EPA Method 624 |
|
*Surchargeable
Parameters |
NOTES:
All sampling procedures must be in accordance with 40 CFR Part 136 and EAJSA Rules and Regulations.
Sample preservation must be performed immediately upon sample collection. Any self-monitoring conducted at the designated sample location (outlined in permit) which is in accordance with EPA approved procedure must be reported to the EAJSA (please note 1/28/00 memo). When using a different method for analysis you must notify the EAJSA prior.
References:
40 CFR Part 136
EPA's Industrial User Inspection And Sampling Manual for POTWs (EPA 831-B-94-001).
Easton Area Joint Sewer Authority Rules and Regulations.
|