Sampling Requirement
| Parameters |
Bottle Type | Sample Type | Preservative | Holding Time | Sampling Method |
| Ammonia as N [NH3N]* | Pint Plastic | Composite | H2SO4 to pH <2cool to 4° C | 28 days | EPA 350.1 |
| Arsenic | Pint Plastic | Composite | HNO3 to pH <2 coolto 4° C | 6 months | EPA 200.7 |
| BOD* | ½ Gal. Plastic | Composite | None cool to 4° C | 48 hours | SM 5210B |
| Cadmium | Pint Plastic | Composite | HNO3 to pH <2 cool to 4° C | 6 months | EPA 200.7 |
| Chromium | Pint Plastic | Composite | HNO3 to pH <2 cool to 4° C | 6 months | EPA 200.7 |
| Color (Purity & Luminance) |
Pint Plastic |
Grab | None cool to 4° C | 48 hours | SM 2120 |
| Copper | Pint Plastic | Composite | HNO3 to pH <2 cool to 4 ° C | 6 months | EPA 200.7 |
| Cyanide | Pint Plastic |
Grab | NaOH to pH >12 cool to 4° C | 14 days | SM 4500 |
| Lead | Pint Plastic | Composite | HNO3 to pH <2 cool to 4 ° C | 6 months | EPA 200.7 |
| Mercury | Pint Plastic |
Composite | HNO3 to pH <2 cool to 4 ° C | 6 months | EPA 600 245.1 |
| Molybdenum | Pint Plastic | Composite | HNO3 to pH <2 cool to 4 ° C | 6 months | EPA 200.7 |
| Nickel | Pint Plastic | Grab | HNO3 to pH <2 cool to 4 ° C | 6 months | EPA 200.7 |
| Total Oil & Grease |
Quart Glass |
Grab | H2SO4 to pH <2 cool to 4° C | 28 days | EPA 1664 HEM |
| Total Petroleum Hydrocarbons |
Quart Glass |
Grab |
HCl to pH <2 cool to 4° C | 28 days | EPA 1664 SGT |
| Phenols | 500 ml Amber Glass |
Grab | H2SO4 to pH <2 cool to 4° C | 28 days | EPA 420.2 |
| Selenium | Pint Plastic | Composite | HNO3 to pH <2 cool to 4° C | 6 months | EPA 200.7 |
| Silver | Pint Plastic |
Composite | HNO3 to pH <2 cool to 4° C | 6 months | EPA 200.7 |
| TSS* | Pint Plastic |
Composite | HNO3 to pH <2 cool to 4° C |
7days | SM 2540D |
| Zinc | Pint Plastic | Composite |
HNO3 to pH <2 cool to 4° C | 6 months | EPA 200.7 |
| Volatiles | 3 - 40ml VOA Vials | Grab | Zero headspace HCl to pH <2 cool to 4° C | 14 days | EPA 624 |
*Surchargeable Parameters
NOTES:
All sampling procedures must be in accordance with 40 CFR Part 136 and EAJSA Rules and Regulations.
Sample preservation must be performed immediately upon sample collection. Any self-monitoring conducted at the designated sample location (outlined in permit) which is in accordance with EPA approved procedure must be reported to the EAJSA (please note 1/28/00 memo). When using a different method for analysis you must notify the EAJSA prior.
References:
40 CFR Part 136
EPA’s Industrial User Inspection And Sampling Manual for POTWs (EPA 831-B-94-001).
Easton Area Joint Sewer Authority Rules and Regulations.

EAJSA
Disclaimer
Users please note: The information and resources on this website are provided as a service by the Easton Area Joint Sewer Authority to it’s customers, municipal members, staff, the community and to other users of the internet. The Authority makes no warranty to the user, either express or implied, of the contents of this site or of the other sites to which it links.
MAP